Pilot Evaluation of Possible Airborne Transmission in a Geriatric Care Facility Using Carbon Dioxide Tracer Gas: Case Study

Ishigaki Y, Yokogawa S, Minamoto Y, Saito A, Kitamura H, Kawauchi Y

Pilot Evaluation of Possible Airborne Transmission in a Geriatric Care Facility Using Carbon Dioxide Tracer Gas: Case Study

JMIR Form Res 2022;6(12):e37587

DOI: 10.2196/37587

PMID: 36583933

PMCID: 9840100

Pilot Evaluation of Possible Airborne Transmission in a Geriatric Care Facility Using CO2 Tracer gas: A Case Study

  • Yo Ishigaki; 
  • Shinji Yokogawa; 
  • Yuki Minamoto; 
  • Akira Saito; 
  • Hiroko Kitamura; 
  • Yuto Kawauchi

ABSTRACT

Background:

Ventilation plays an important role in controlling aerosol transmission of coronavirus disease (COVID-19), and mass transmission of COVID-19 has been reported in poorly ventilated areas.

Objective:

A real-world mass infection outbreak which occurred in an elderly nursing home, in Miyagi Prefecture, Japan, was simulated experimentally and numerically to investigate the controlling factors and quantify the effectiveness of various natural ventilation settings by means of air change rate (ACR).

Methods:

Using the CO2 tracer gas method, the ACR values at the time of the outbreak were estimated to be 2.0–6.2 h-1 in rooms in the facility. Furthermore, a low-cost intervention of opening windows improved the ventilation frequency by a factor of 1.48–5.74. This implies that advective fluid flows are the key in the spread of high CO2 concentration zones. A numerical simulation was performed to obtain spatio-temporal evolution on such high CO2 concentration zones under similar conditions to the present experiment.

Results:

The results showed that ventilation was significantly dependent on the window opening conditions in all rooms (p-values ranging from 0.001 to 0.03 for all the rooms). In contrast, there was no significant dependence on the location of the sensor in any of the areas. Development of high CO2 concentration zones occurs in the first few minutes. Furthermore, the leading edge of such zones towards the common room yields a relatively high fluid velocity, suggesting that the large-scale advective flow dictates the spread of such high CO2 concentration zones.

Conclusions:

The present results suggest that secondary infections could occur due to the aerosol advection driven by such large-scale flows, even when the building design adheres the ventilation guidelines. In elderly care facilities, open architectural spaces are recommended to realize quality of life and monitor residents. However, management is required to reduce the downwind infection risk from aerosols and ACR.


 Citation

Please cite as:

Ishigaki Y, Yokogawa S, Minamoto Y, Saito A, Kitamura H, Kawauchi Y

Pilot Evaluation of Possible Airborne Transmission in a Geriatric Care Facility Using Carbon Dioxide Tracer Gas: Case Study

JMIR Form Res 2022;6(12):e37587

DOI: 10.2196/37587

PMID: 36583933

PMCID: 9840100

Download PDF


Request queued. Please wait while the file is being generated. It may take some time.

© The authors. All rights reserved. This is a privileged document currently under peer-review/community review (or an accepted/rejected manuscript). Authors have provided JMIR Publications with an exclusive license to publish this preprint on it's website for review and ahead-of-print citation purposes only. While the final peer-reviewed paper may be licensed under a cc-by license on publication, at this stage authors and publisher expressively prohibit redistribution of this draft paper other than for review purposes.